Protection set for a steady load has proven it trips on a fault. AI load produces fast transients, so the settings have to be shown ignoring a surge and still acting on a fault.

Testing protection settings means applying the transient electrical spikes of AI racks and checking that protection stays closed on a surge and still operates on a fault. Base build testing proves the settings at the riser under the full IT load. End-of-line testing applies the surges at each rack position, where local protection sits, so settings and discrimination are adjusted against measured behaviour.
A trip found in testing is a settings change. The same trip in a live hall is an outage.
Whether a healthy circuit opens on a fast load change.
Whether the right device operates first during a real transient.
Whether inrush during a restart sequence is read as a fault.
A rare event reproduced on demand, and captured in the log.
Protection is first checked under full load, then against the load as the racks will apply it.
Base buildLB500, LB600 or LB700 load the circuits at the riser
End-of-lineLCLB 160 and LCLB 240 apply surges at each rack position, with solid-state switching
See the end-of-line rangeThe load is repeatable from one controller, so a surge that caused a trip can be applied again.

Tell us the protection arrangement and the IT load. We will help you specify the transient test.