Sizing tool

Size your PowerLoad test in seconds

Answer a few quick questions about your CDUs or racks. The tool works out how many PowerLoad units the test needs, CDU by CDU.

  1. Type
  2. CDUs
  3. Plan
  4. Sizing

What are you testing?

Pick one. You can switch at any point.

How the sizing works

Sized CDU by CDU, not from the total

Each CDU is tested on its own load, so the tool sizes one CDU first and then multiplies. Dividing the hall total by the unit size can come up short. Six 905.2kW CDUs total 5,431kW, which looks like 11 LB500s, yet each CDU needs two, so the test takes 12.

Base build testing

The LB500, LB600 and LB700 prove the CDUs, chillers and risers while the hall is built. The tool flags the unit that tests each CDU with the fewest units and the least spare capacity.

End-of-line testing

The LCLB 160 and LCLB 240 replicate the liquid-cooled share of each rack, and the ACLB 60 adds the air-cooled share, split the way the design specifies.

Confirmed per project

The output here is indicative. Up to 250 units run from one controller, and the final configuration is confirmed against your design, your single line and your coolant loop.

Get an exact spec for your hall