The manifold trolley and the flushing and refill cart prepare a liquid cooling loop before load testing, so it is clean, filled and balanced. They support both the base build and end-of-line ranges.
The trolley connects the load banks to the hall pipework, with a flow meter and pressure sensor on every outlet, so each circuit is balanced and measured.
Dual 4 inch manifolds, inlet on top and outlet below, with 316 stainless on every part the coolant touches. Each outlet is measured for flow and pressure drop, so every circuit balances independently.
A dual-pump cart with a 250L tank and 316 stainless on everything the coolant touches. It circulates coolant through a 25 micron filter to strip out swarf and debris, vents trapped air, then fills the loop ready for load testing.
The cart and the trolley prepare the loop before the load bank, so the loop the load bank tests is the loop that will run. Once the hall is live, the cart keeps it clean.
The cart circulates coolant through the 25 micron filter to clear swarf and debris, vents trapped air, then charges the loop from its 250L tank. The system starts clean.
The trolley splits one feed into regulated outlets, each with a flow meter and pressure sensor, so every branch is balanced and measured.
With the loop clean and balanced, the load bank applies load at the rack. Flow and pressure feed back over I/O Link and BACnet, so results reflect real conditions.
In a live hall, isolate a rack, drain it, then flush, clean and refill its GPUs from the cart before it goes back into service.
The supporting kit that prepares a liquid-cooled loop before a load bank ever applies load. It flushes and fills the pipework, then distributes and regulates the coolant across each rack circuit. PowerLoad supplies a flushing and refill cart that cleans and charges the loop through a 25 micron filter, and a manifold trolley that splits one feed into regulated, individually metered outlets.
New pipework carries swarf, debris and trapped air that will foul cold plates and CDUs once the system is live. The refill cart circulates coolant through a 25 micron filter to remove that contamination and de-aerates the loop, so the load bank proves a clean, representative system rather than a dirty one. More on the flushing and refill cart.
It splits one coolant feed into regulated outlets, so each circuit can be balanced independently. A digital flow meter and pressure sensor on every outlet measure flow and pressure drop, feeding data back over I/O Link to a BACnet interface that integrates with the load bank system.
Yes. Both pieces share the FD83, Tri-clamp and UQD connection standards used across the PowerLoad load banks, so the equipment connects straight to the load banks.
Yes. The manifold trolley and the flushing and refill cart are available to hire alongside the load banks. Speak to the team about availability for your project.
Yes. The higher-capacity liquid-cooled units, such as the 700kW LB700, can be applied to chiller and larger cooling-plant testing as well as rack and CDU testing, wherever the design needs a heavier heat load than a single 500kW unit provides.
PowerLoad equipment is built for a range of site conditions, including outdoor testing applications. The exact ingress-protection specification is being confirmed, so speak to the team about your site conditions before assuming a specific rating.
Specifications for the kit that cleans, fills, distributes and regulates the coolant loop.