Home/Projects/Slough, United Kingdom
United Kingdom · Liquid retrofit · CDU and rack level testing

A 2MW test on a
liquid retrofit

A liquid-cooled retrofit in Slough, tested at the CDU and at rack level.

Project details

Client
Global Colocation Giant
Location
Slough, UK
Solution provided
CDU & Rack Level Testing
Project type
Load bank testing

As recorded by PowerLoad. Client names are not published.

2MWTest
500kWLiquid load bank
160kWGPU emulator
1Manifold trolley
A PowerLoad 500kW liquid-cooled load bank connected in a Slough data hall
Scope

What is on the record

A liquid load bank, a GPU emulator and a manifold trolley, testing at the CDU and at rack level.

  • Liquid Retrofit
  • AI GPU Rack Level Testing
  • Liquid Cooled
  • 160kW GPU Emulator
  • 500kW Liquid Load Bank
  • Commissioning Manifold Trolley
  • 2MW Test
  • Heat Load Test
  • Client Load Test
  • Advanced Commissioning Reporting

Reproduced from PowerLoad's own project record.

A PowerLoad commissioning manifold rig in a Slough data hall
The equipment

Regulated outlets from one riser

The commissioning manifold trolley is a 304-grade stainless trolley carrying dual 4 inch manifolds. It distributes the riser feed to regulated outlets, each with its own flow meter and pressure sensor, so every rack is balanced and measured independently rather than averaged across the row.

Flow and pressure feed back over I/O Link and BACnet while the load bank applies load.

Specification from the PowerLoad Commissioning Equipment page. Not specific to this project.

Talk to us about your hall
On the record

The equipment listed

Liquid Load Bank 500kW

Liquid Load Bank

Integrates directly with the cooling loop, so the CDU and coolant path are proved under load.

On the record
A PowerLoad LCLB 160 GPU emulator 160kW

LCLB 160 GPU emulator

True rack-level heat and electrical load, replicating how the GPUs will behave.

On the record
Commissioning Manifold Trolley Manifold

Commissioning Manifold Trolley

Regulated outlets, each metered for flow and pressure drop.

On the record
The workflow

Where the trolley sits in the sequence

This is the PowerLoad commissioning sequence the manifold trolley belongs to. It is how the equipment is designed to be used, not a log of this project.

Flush and fill

The cart circulates coolant through a 25 micron filter to clear swarf and debris, vents trapped air, then charges the loop from its 250L tank.

Distribute and regulate

The trolley distributes the riser feed to regulated outlets, one per rack, each with a flow meter and pressure sensor.

Load and prove

With the loop clean and balanced, the load bank applies load at the rack. Flow and pressure feed back over I/O Link and BACnet.

The kit

What it looks like on the floor

500kW liquid-cooled bank connected in the hall
500kW liquid-cooled bank connected in the hall
The manifold, overhead
The manifold, overhead
Two 500kW units
Two 500kW units
A PowerLoad engineer on the control panel
A PowerLoad engineer on the control panel
Test data captured on site
Test data captured on site

PowerLoad equipment on site in Slough. The operator is not named, and the building is not identified.

More projects

The other halls

Planning a similar project?

Tell us the hall, the IT load and the programme. We will size the load banks, emulators and commissioning support around it.